RM SERIES 5-10 KVA

FFATURES

  • Online-Double conversion
  • Non Transfer Time of output
  • PFC technology
  • Full digital control (DSP)
  • Output power factor: 0.9
  • Input current harmonic: 3%
  • ECO function
  • Charging/Rectifier/Inverterfully digital control technology
  • Optimization battery group, the quantity of battery: 16/18/20 pieces (optional)
  • Wide input voltage range: 120~276Vac
  • Wide input frequency range: 45~55HZ/54~66Hz±0.5Hz
  • Self-testing when UPS startup
  • Input over/under-voltage protection
  • Automatic bypass
  • DC start
  • Communication port: RS232, USB Options: SNMP card / Relay card
  • Rack Mountable
  • SURGE ENERGY RATING 450 JOULES
Enquiry Now
Category:

Technical Specifications

MODEL RM6KVA RM10KVA
Capacity (VA/Watts) 5k/4.5k 10k/9k
INPUT
Nominal voltage 220/230/240Vac(L+N+PE)
Operating voltage range 100-285Vac
Operating frequency range 40–70 Hz
Power factor ≥0.99
Bypass voltage range 220V: +25% (optional +10%,+15%,+20%)
230: +20% (optional +10%,+15%)

240: +15% (optional +10%)
Min. voltage: -45% (optional -20%,-30%)

ECO range Same as bypass
Harmonic distortion (THDi) <3%(100% linear load)
Generator input Support
OUTPUT
Output voltage 220/230/240Vac
Power factor 0.9
Voltage regulation ±2%
Frequency Line Mode ± 1%/±2%l ± 4%l ± 5%/± 10% of the rated frequency(optional)
Bat. Mode 50/60 (±0.1)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load
≤5% with non linear load
Waveform Pure Sinewave
Efficiency >93.5%
BATTERY
Battery voltage Optional Voltage: ±96/±108/± 120Vdc
Typical recharge time 6-8 hours (to 90% of full capacity)
Charge current Maximum Current 6A; charge current can be set according to battery capacity installed.
SYSTEM FEATURES
Transfer time Utility to Battery: Oms; Utility to bypass: Oms
Overload Line Mode Load ≤110%: Cont. ; ≤125%: last 10min; ≤150%: last 1S; >150% turn to bypass mode
Bypass Mode 40A (Input breaker) 60A (Input breaker)
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
Self-diagnostics Upon Power On and Software Control
EPO (optional) Shut down UPS immediately
Battery Advance Delivery management
Noise Suppression Complies with EN62040-2
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading on the LCD display Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage,
Inner Temperature & Remaining Battery Backup Time
Comunication interface USB,RS232, Parallel Port, SNMPcard/Relay card (optional)
ENVIRONMENTAL
Operating temperature 0-40°C
Storage temperature -25-55°C
Humidity range 0-95% (non condensing)
Altitude <1500m
Noise level <55dB
PHYSICAL
Dimension WxH×D (mm) 443× 131×580(3U)
Net Weight (kg) 23 25
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
Protection INPUT OVER VOLTAGE PROTECTION, INPUT UNDER VOLTAGE PROTECTION, OVER VOLTAGE CUT OFF. SHORT CIRCUIT PROTECTION,
OVER TEMPERATURE, LOW BATTRY & BATTERY OVER CHARGE PROTECTION SHOULD BE PROVIDED. BUILT IN BYPASS SWITCH
    • All specifications are subject to change without prior notice.
    • Custom-made specitications are acceptable.