Menu Close

Shop

HP Series

Features:

  • Advanced DSP and 3-level technology
  • Output power factor 0.9/1.0
  • Active power factor correction (APFC), input power factor up to 0.99
  • High efficiency 94% (up to 98% in ECO mode)
  • Advanced digital parallel technology
  • Wide input voltage range (110 – 288 Vac) and frequency range (40~70 Hz)
  • 50/60 Hz frequency auto sensing
  • Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output
  • Dual-input design, supporting independent bypass
  • Flexible battery configuration (settable 16-20 pcs batteries) Digitally controlled charger
  • High charging current available (Max. 12 A)
  • Charging voltage and current configured by demands
  • Linear derating in low voltage input reducing battery discharging times, extending the service life of battery
  • Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%
  • Ability to switch on the UPS with batteries
  • Settable delayed start time when mains power is restored, reducing the impact on power grid or generator
  • Fan speed varies intelligently with temperature, reducing noise and extending its service life
  • Equipped with self-aging function
  • Compact internal layout, miniaturized the complete unit for small footprint
  • LCD+LED display, multi-functional keys operation, friendly human-machine interface
  • Powerful background software for parameters configuration Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces
  • Effective software and hardware protection function, robust self- diagnostic function, and abundant event log for check
  • Available Options
  • In-built isolation transformer either at input or output RS232 and smart card slot included
  • Optional parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms
Enquiry Now
Category:

specification

MODEL HP 1005 / HP 1006 HP 1010 / 10KVAH
Capacity 6 kVA / 5.4 kW 6 kVA / 6 kW 10 kVA / 9 kW 10 kVA / 10 kW
INPUT
Input Wiring Single-phase three-wire (1 Φ + N + PE)
Rated voltage 208 / 220 / 230 / 240 Vac
Voltage range 140 – 276 Vac
Rated Frequency 50 / 60 Hz (auto sensing)
Frequency Range 40 ~ 270 Vac
Power factor ≥ 99
Bypass voltage range -40% ~ +15% (settable)
Total harmonic distortion (THDi) ≤ 5%
OUTPUT
Output wiring Single-phase (1 Φ + N + PE)
Rated voltage 208 (PF=0.9)/ 220 / 230 / 240 Vac
Voltage regulation ±1%
Frequency Synchronized to bypass in mains mode; 50 / 60 ± 0.1 Hz in battery mode
Waveform Sinusoidal
Power factor 1
Total harmonic distortion (THDv) ≤ 2% (linear load); ≤5% (non-linear load)
Crest factor 3:1
Overload 105% ~ 110% for 10 mins, 110% ~ 125%: 1 min, 126% ~ 150%: 30 s
BATTERIES
DC voltage 168 Vdc / 192 Vdc / 240 Vdc (settable)
Number of battery 14 pcs / 16 pcs / 20 pcs (settable)
Charging current Standard model: 1 A; Long time model: 5 A (default), 1 – 12 A (optional, PF 0.9)
Recharge time Standard model: 90% capacity restored in 8 hours; Long time model: depends on battery capacity
SYSTEM
Efficiency ≥ 90% at 100% load, max. 94% at 60% load, ≥98% in ECO mode
Transfer time 0 ms
Protection Short circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage, and fan failure
Max. number of parallel units 4
Communications RS232 (Standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display LCD + LED
OTHERS
Operating temperature 0 – 40°C
Storage temperature -25°C – 55°C (without battery)
Relative humidity 0 – 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1 m ≤ 55 dB ≤ 58 dB
Dimensions (W x D x H)(mm) 191 x 465 x 711 (S), 191 x 465 x 350 (H) 191 x 495 x 711 (S), 191 x 495 x 350 (H)
Packaged Dimensions (W x D x H)(mm) 310 x 654 x 941 (S), 318 x 595 x 475 (H) 310 x 685 x 941 (S), 318 x 617 x 475 (H)
Net weight (kg) 53 (S), 14.5 (H) 62 (S), 16.5 (H)
Gross weight 61 (S), 16 (H) 70 (S), 18 (H)

Description

Rear Panel

  • RS232
  • ΕΡΟ
  • Parallel Port (optional)
  • USB (optional)
  • Temperature Detection (optional)
  • Intelligent Slot
  • Reserved: for manual bypass or battery
    breaker or outlets ect.
  • Fans
  • Bypass Breaker
  • Input Breaker
  • GND
  • Terminals and Cover

Reviews

There are no reviews yet.

Be the first to review “HP Series”